Rockwell Automation 57C415 24V AC/DC Input Module User Manual

Page 19

Advertising
background image

5Ć3

configuration task. Verify that the register number and bit

number are correct.
For remote I/O installations, also verify that the master slot

and remote drop number are defined correctly.

Step 2.

Verify that the module can be accessed.
Connect the programming terminal to the system and run

the ReSource Software. Use the I/O MONITOR function to

display register 0. If the programmer is able to monitor the

inputs, the problem lies in the application software

(proceed to step 3). If the programmer cannot monitor the

inputs, the problem lies in the hardware (proceed to step

4).

Step 3.

Verify that the user application program is correct.
This module cannot be written to. If a BASIC task caused

the bus error, the error log will contain the statement

number in the task where the error occurred. If a ladder

logic or control block task caused the error, you will need

to search the task for any instances where you used an

input as a ladder logic coil or wrote to it in a control block

task.

Step 4.

Verify that the hardware is working correctly.
Verify the hardware functionality by systematically

swapping out the input module, processor module(s), and

backplane. After eachswap, if the problem is not

corrected, replace the original item before swapping out

the next item.
For remote I/O installations, systematically swap out the

input module, the slave remote module, and the

backplane. After eachswap, if the problem is not

corrected, replace the original item before swapping out

the next item.