Rockwell Automation 2080-LC30-10QWB_10QVB Micro830 10 Point Programmable Controllers User Manual

Page 14

Advertising
background image

14 Micro830 10 Point Programmable Controllers

Publication 2080-IN002B-EN-P - April 2014

Insulation stripping
length

7 mm (0.28 in.)

Enclosure type rating

Meets IP20

North American temp
code

T4

(1)

Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation
Wiring and Grounding Guidelines, publication

1770-4.1

.

Input Specifications

Attribute

High-speed DC input
(Inputs 0…3)

Standard DC input
(inputs 4 and higher)

Number of inputs

4

2

Input group to
backplane isolation

Verified by one of the following dielectric tests: 1,414V DC for 2 s
75V DC working voltage (IEC Class 2 reinforced insulation)

Voltage category

24V DC sink/source

Off-state voltage, max

5V DC

On-state voltage range

16.8…26.4V DC @ 65°C (149°F)
16.8…30.0V DC @ 30°C (86°F)

10…26.4V DC @ 65°C (149°F)
10…30.0V DC @ 30°C (86°F)

Off-state current, max

1.5 mA

On-state current, min

5.0 mA @ 16.8V DC

1.8 mA @ 10V DC

On-state current, nom

7.6 mA @ 24V DC

6.15 mA @ 24V DC

On-state current, max

12.0 mA @ 30V DC

Nominal impedance

3 k

Ω

3.74 k

Ω

IEC input compatibility

Type 3

AC input filter setting

8 ms for all embedded inputs
In Connected Components Workbench, go to the Embedded I/O
configuration window to reconfigure the filter setting for each
input group.

Output Specifications

Attribute

2080-LC30-10QWB

2080-LC30-10QVB

Relay Output

High-Speed Output
(Outputs 0…1)

Standard Output
(Outputs 2…3)

Number of outputs

4

2

2

General Specifications

Attribute

2080-LC30-10QWB

2080-LC30-10QVB

Advertising