Dimensions – Rockwell Automation 2097-PGMR Memory Module Programmer Quick Start User Manual
Page 14

14 Bulletin 2097 Memory Module Programmer
Publication 2097-QS001D-EN-P - November 2011
Dimensions
TRANSFER FAILED
Error in the data transmission to the EPM port,
because the memory chip is defective, or is not
placed correctly in the port.
Exchange the defective memory module or plug
the memory module correctly in the port.
Attempted MASTER -> EPM transfer when the
memory size of the master memory module is
different from that of the target.
Replace the memory module in the EPM port
with a memory module of the same color as the
master.
Error in the data transmission to the EPM port,
because of an internal error in the memory
module programmer.
Contact your Rockwell Automation
representative.
INVALID OPTION!
Attempted to create a new file from a servo
drive memory module in the master port.
Function not available.
INVALID EPM!
Attempted to edit a memory module.
Function not available.
NO FILES
Attempting to edit, delete, or create a file, but
there are no stored files in the memory module
programmer.
Function not available.
CFG EPM MISSING!
Attempted to LOAD CFG EPM.
Function not available.
Troubleshooting (continued)
Description
Possible Cause
Corrective Action
COPY
105
(4.1)
76
(3.0)
155
(6.1)
4
(0.16)
Dimension are in mm (in.).