Rockwell Automation 2100 Install Neutral Connection Plate User Manual

Centerline

Advertising
background image

2100-IN011A-EN-P - November 2000

CENTERLINE

®

Motor Control Centers

Install Neutral Connection Plate in Bulletin
2100 Section

Catalog Numbers: 2100H-NPC1, 2100H-NPC2, 2100H-NPC3,
2100H-NPS1, 2100H-NPS2, 2100H-NPS3

Instructions

Application

Use these instructions to install a neutral connection plate in a Bulletin 2100
motor control center section. Instructions apply to the following kits:

Catalog number 2100H-NPC1 and 2100H-NPS1 (for top horizontal
wireway)

Catalog number 2100H-NPC2 and 2100H-NPS2 (for incoming line
compartment or for 0.5 space factor units)

Catalog number 2100H-NPC3 and 2100H-NPS3 (for bottom horizontal
wireway)

Recommended Tools

Screwdriver, 5/16” and 7/16” wrench or socket, torque wrench

Installation

Refer to Figure 1, 2, or 3, and use the following steps to install a neutral
connection plate:

1. Make sure that all power has been disconnected.

2. Remove the unit support pan or top horizontal wireway pan from the

appropriate location. (See Publication 2100-5.0 for removal
instructions.)

3. Replace the unit support pan or top horizontal wireway pan with the

modified unit support pan or modified horizontal wireway pan.
If there is interference from other parts, unassemble the neutral
connection plate assembly from the pan, and install the pan.

4. If necessary, reattach the neutral plate assembly. Torque to 45 lb-in

(5 N-m).

5. For catalog numbers 2100H-NPC3 and 2100H-NPS3 (for bottom

horizontal wireway): If unit support pan removed in Step 1 has a latch/
interlock bushing installed, remove this bushing and reinstall it on the
pan supplied with the kit. Torque to 32 lb-in (3.6 N-m).

Important: If the feed to the neutral connection plate kit is separated from

the phase conductors by a complete path of magnetic material,
the current that is feeding the neutral connection plate kit must
not exceed 280 amperes rms. Lug supplied has a wire capacity
of #6-250 kcmil and should be torqued to 370 lb-in (41.8 N-m).

!

ATTENTION: De-energize all power sources to the motor
control center before installing neutral connection plate.
Failure to de-energize all power sources can result in severe
injury or death.

Advertising