Rockwell Automation Dual AC/DC Input Module/AutoMate/AutoMax/DCS User Manual
Module specifications, Module location, Ambient conditions

AutoMate®/DCS-5000/AutoMax®
Dual A-C/D-C Input Module
120V (M/N 45C40)
240V (M/N 45C43)
24V (M/N 45C44)
Module Specifications
Module Location
• Plugged into an I/O Rail (M/N 45C1)
Ambient Conditions
• Operating Temperature
(at the module):
32 to 140°F (0 to 60°C)
• Storage Temperature:
—4 to 185°F (—20 to 85°C)
• Humidity:
5 to 90% (Non-Condensing)
Module Dimensions
• Height:
13
/
16
inches (2.1 cm)
• Width:
3 inches (7.6 cm)
• Depth:
6
1
/
16
inches (15.5 cm)
• Weight:
5 ounces (140 grams)
Input Circuit
• Number of Inputs:
2 Channels
• Response Time:
9.5ms at 60 HZ
• Turn-On Time:
2.0ms after threshold is exceeded
• Turn-Off Time:
19.0ms after threshold is removed
• Electrical Isolation:
(1) 2500 V (RMS) isolation between the
input circuit and the logic circuit
(2) 1000 V (RMS) channel to channel isolation
• Frequency:
D-C or 48/63 Hz
• M
aximum Short Circuit Power Source: 10 KVA
J-3736-1
M/N 45C40
M/N 45C43
M/N 45C44
Nominal A-C/D-C Voltages
115V
230V
24V - 28V
On Threshold A-C Voltages
80V
150V
16.5V
On Threshold D-C Voltages
108V
203V
20V
Off Threshold A-C Voltages
60V
120V
10.5V
Off Threshold D-C Voltages
83V
165V
14.5V
Maximum Input Voltage
130V
255V
40V
Impedance at Nominal Voltage
18.1K Ohms
52.8K Ohms
3.6K Ohms