Rockwell Automation Dual AC/DC Input Module/AutoMate/AutoMax/DCS User Manual

Module specifications, Module location, Ambient conditions

Advertising
background image

AutoMate®/DCS-5000/AutoMax®

Dual A-C/D-C Input Module

120V (M/N 45C40)
240V (M/N 45C43)

24V (M/N 45C44)

Module Specifications

Module Location

• Plugged into an I/O Rail (M/N 45C1)

Ambient Conditions

• Operating Temperature

(at the module):

32 to 140°F (0 to 60°C)

• Storage Temperature:

—4 to 185°F (—20 to 85°C)

• Humidity:

5 to 90% (Non-Condensing)

Module Dimensions

• Height:

13

/

16

inches (2.1 cm)

• Width:

3 inches (7.6 cm)

• Depth:

6

1

/

16

inches (15.5 cm)

• Weight:

5 ounces (140 grams)

Input Circuit

• Number of Inputs:

2 Channels

• Response Time:

9.5ms at 60 HZ

• Turn-On Time:

2.0ms after threshold is exceeded

• Turn-Off Time:

19.0ms after threshold is removed

• Electrical Isolation:

(1) 2500 V (RMS) isolation between the
input circuit and the logic circuit
(2) 1000 V (RMS) channel to channel isolation

• Frequency:

D-C or 48/63 Hz

• M

aximum Short Circuit Power Source: 10 KVA

J-3736-1

M/N 45C40

M/N 45C43

M/N 45C44

Nominal A-C/D-C Voltages

115V

230V

24V - 28V

On Threshold A-C Voltages

80V

150V

16.5V

On Threshold D-C Voltages

108V

203V

20V

Off Threshold A-C Voltages

60V

120V

10.5V

Off Threshold D-C Voltages

83V

165V

14.5V

Maximum Input Voltage

130V

255V

40V

Impedance at Nominal Voltage

18.1K Ohms

52.8K Ohms

3.6K Ohms

Advertising