4 rack replacement – Rockwell Automation 57C332 AutoMax Power Supply Module and Racks User Manual

Page 22

Advertising
background image

3Ć6

Wire Color

Wire Label

Power Supply

Faceplate Connector

black

L2

L2

orange

L1

L1

green

-

GND

e) If you are using the Battery BackĆUp unit, plug one end

of the Battery BackĆUp cable into the Power Supply

module faceplate connector labeled BATTERY BACK

UP". Plug the other end into the Battery BackĆUp unit.

Rotate the keyswitch on the front panel from Memory

Protect to the Program position.

f) Using a screwdriver, reĆattach the nameplate bracket to

the base of the rack.

Step 5.

Turn on power to the system.

Step 6.

Verify the installation by connecting the personal computer

to the port labeled PROGRAMMER/PORT B" on the

leftmost Processor in the Rack and running the ReSource

programming software. Try to read from or write to the

registers on each of the modules in the Rack.

WARNING

BE CAREFUL TO INSURE THAT NO UNEXPECTED MACHINE MOTION WILL

RESULT WHEN WRITING TO OUTPUTS. FAILURE TO OBSERVE THIS

PRECAUTION COULD RESULT IN BODILYINJURYOR DAMAGE TO EQUIPMENT.

Refer to the instruction manuals describing the specific

hardware in the installation for more information.

3.4

Rack Replacement

Use the following procedure to replace the Rack:
Step 1.

Turn off power to the Rack and all connections.

DANGER

THE POWER SUPPLYMODULE OPERATES USING AC INPUT VOLTAGE

CAPABLE OF PRODUCING SEVERE SHOCK. MAKE CERTAIN THAT THE

EXTERNAL AC SUPPLYCIRCUIT IS TURNED OFF BEFORE INSERTING OR

REMOVING THE MODULE OR ANYCONNECTING WIRES. FAILURE TO

OBSERVE THIS PRECAUTION COULD RESULT IN SEVERE BODILYINJURYOR

LOSS OF LIFE.

Step 2.

Using a screwdriver, remove the nameplate bracket from

the rack by removing the three screws near the base

holding it to the cable guide area. Loosen all the screws

holding connectors to the modules in the Rack. Remove

the connectors. Disconnect the wires attached to the

terminal strip on the Power Supply module.

Step 3.

Use a screwdriver to loosen the screws holding all

modules, including the Power Supply module, in the Rack.