Replacing the snubber assembly, Concluding steps – Rockwell Automation 2361 Snubber Assembly Replacement (T-Frame) User Manual
Page 5
Advertising

Snubber Assembly Replacement (for 3000A 1395 DC Drives)
5
Publication 2361-5.19 - June 1998
Replacing the Snubber Assembly
1.
Mount the new snubber assembly in place with the two mounting
bolts and torque to 10 lb-ft.
2.
Secure the snubber lead to the output busbar.
3.
Secure the snubber lead to the input busbar.
4.
Latch the Glastic armature-pulse transformer panel in place.
Concluding Steps
After installing the snubber assembly, replace all Lexan shielding and
secure the bridge bay door. Dispose of old parts according to your
company procedures and local ordinances.
Advertising
This manual is related to the following products: