Kinetix 6000M Hybrid Cable 5

Publication 2090-IN032B-EN-P - March 2012

Install the Cable

Follow these steps when installing a 2090-CHBP8S8-12AA

xx hybrid cable.

1. Verify power to the IPIM module is removed before making any connections or

disconnecting any components of the system.

2. Before beginning any cable bend, determine the recommended installation areas, and the

clearance required from the features shown in the diagram.

Clearance from these areas should be greater than or equal to the cable diameter.

3. Keep cable bends within the bend radius listed in the Specifications on

page 7

.

Hybrid cables have a bend radius of twelve times the cable diameter.

4. Observe these restrictions when installing these cables:

Prevent the cable from flexing within 150 ±25 mm (6 ±1 in.) installation areas.

Bend cables to a specific shape only in the bend zone area.

Provide cable supports at 3 m (10 ft) intervals along the cable run to reduce tension
and flexing at the connectors and other features on the cable.

5. Tighten each M23 connector approximately 45° to fully seat the contacts and secure

each connection.

ATTENTION: Arcing or unexpected motion can occur if cables are connected or disconnected while
power is applied to the IDM system. Before working on an IDM system, disconnect power and wait
the full time interval as indicated in the warning on the IPIM module or verify the DC bus voltage at
the IPIM module measures less than 50V DC.

Failure to observe this precaution could result in severe bodily injury or loss of life, and damage to
the product will occur.

IMPORTANT

The internal O-ring is self-conforming and requires a short period between each
connect/disconnect cycle to expand to full size. Let the O-ring expand for at least 60 seconds
before reconnecting a hybrid cable.

Limited

Bend Zone

Installation Area

300 ± 25 (12 ± 1.0)

Installation Area

300 ± 25 (12 ± 1.0)

Female Connector

Male Connector

2090-CHBP8S8-12AA shown

Dimensions are in mm and (in.).