Fiber Optic Cable Installation For 2364P Parallel Configurations

3

Wiring Guidelines

Fiber optic cables are fragile and can be damaged if not handled properly.
Please adhere to the guidelines shown in Figure 2 when installing the fiber
optic cables.

Figure 2
Wiring GuideLines

Installing the Fiber Optic
Cable(s)

1. Using a meter, test the voltage across the AC line, and across the DC bus.

2. Connect the cables to the R2R boards according to Figure 3. Routing

paths for cables are given in publication 2364P-5.01, Parallel
Configuration–User Manual.

Inspection Precaution: Sharp bends, kinks, and deep nicks in the cable
may greatly affect the performance of the fiber cable. Replacement may
be necessary in these cases.

3 inch (76 mm)

diameter or greater

Radius 1 inch (254 mm)

or greater

Bending Radius

Coiling Excess Cable

Tie Wrap

Do not overtighten tie wraps

The fiber cable should be
able to move freely within
the cable tie wrap.

!

ATTENTION: If there is any voltage present, remove the
source of the voltage. Check for voltages again before
proceeding to the next step.