Rockwell Automation T8424 Trusted TMR 120V ac Digital Input Module User Manual

Sds-8424, Trusted, Industrial control system trusted

Advertising
background image

SDS-8424

Trusted

TM

Industrial Control System

Trusted

TM

TMR 120V ac Digital Input Module-T8424

Issue 2 Jan 2006

FRONT PANEL

DESCRIPTION


The Trusted

TM

TMR 120Vac Digital

Input module interfaces to 40 field
input devices. The module has broad
voltage

thresholds

defined

to

IEC61131-2 and is designed to be
used with Field Termination Assembly
T8823 which provides a current
sourcing interface. Comprehensive
diagnostic tests are performed on
each input channel, including tests for
stuck on and stuck off failures. Fault
tolerance is achieved through Triple
Modular Redundancy (TMR) within
the same module for each of the 40
input channels.

The module provides on-board
Sequence of Events (SOE) reporting
with a resolution of 1ms. A change of
state triggers an SOE entry.

Each triplicated section of the
module, referred to as a slice,
conditions and measures each
channel independently. Each slice is
opto-isolated up to 2500V dc. Each
slice sends its data to a safety layer
hardware voter that presents the
information from all three slices to the
Trusted

TM

TMR Processor. When a

fault is detected on a slice of the
module,

the

Trusted

TM

TMR

Processor

will

flag

the

error,

indicating the need to replace the
module. The Trusted

TM

TMR

Processor will continue to use the
information provided by the remaining
two slices until a replacement module
is available. Replacement modules
can be located in a standby slot next
to the module or in a designated
SmartSlot

with

a

temporary

connection to the same Trusted

TM

Termination Assembly.

Modules may be placed in any I/O
module slot in a Trusted

TM

Processor

Chassis or Expander chassis. Once
the I/O module configuration is set,
mechanical keying is available on all
I/O modules to prevent inserting a
module into an incorrect slot.

Configuration of the module is carried
out using the Trusted

TM

Toolset

running

on

an

Engineering

Workstation. Once configured and
loaded into the Trusted

TM

Controller,

replacement modules are on-line
educated by the TMR Processor.

FEATURES

40 TMR input channels per
module

Comprehensive diagnostics
and self-test

2500V dc Opto-Isolation

On-board 1ms resolution
Sequence of Events reporting

Hot replaceable

Front panel status LEDs for
each channel

Module fault and status
indicators

IEC 61508, SIL 3 safety
applications

T

8

4

2

4

T

ru

s

te

d

T

M

R

1

2

0

V

a

c

D

ig

it

a

l

In

p

u

t

Advertising