Terminal Assignments

Term.# Definition

Default

1

Digital In #1

Stop/ Clr Flt

2

Digital In #2

Start

3

Digital In #3

Function Loss

4

Digital In #4

Jog

5

Digital In #5

Manual

6

Digital In #6

Speed Sel 1

7

+24VDC Int. Common

Logic
Input Supply
Terminals

8

Logic Input Common

9

+24VDC Output

10

+10VDC Ref. Supply

11

Relay Out #1 - NO

/Fault*

12

Relay Out #1 - C

13

Relay Out #1 - NC

14

Analog In #1 Volts (-)

Not
Assigned

15

Analog In #1 Volts (+)

16

Analog In #1 (4-20ma)

Default 4-20 mA
Input

17

Analog In #1 (4-20ma)

18

Analog In #2 Volts (-)

Default 0-10 VDC
Input

19

Analog In #2 Volts (+)

20

Analog In #2 (4-20ma)

Not
Assigned

21

Analog In #2 (4-20ma)

22

Analog Common

Analog Output

23

Analog Out Volts (+)

Output Freq. (Hz)

24

Relay Out #2 - NO

Running*

25

Relay Out #2 - C

26

Relay Out #2 - NC

D-2992

* Form C Relay contact outputs:
NO (Normally Open)
NC (Normally Closed)
C (Common)

Reference Wiring

Analog Reference Wiring
(0 to 10 VDC Input)

(P90) Speed Ref A Sel = Analog In1
(P91) Speed Ref Hi = 60 Hz.
(P92) Speed Ref Lo = 0 Hz.
(P320) Analog In Config =..xx00
(P322) Analog In 1 Hi = 10.0 V
(P323) Analog In 1 L0 = 0.0 V
Analog Inputs can be configured for 4-20
mA. See instruction manual.

Analog Output Wiring
(0 to 10 VDC Output)

(P341) Analog Out Absolute = 1
(P342) Analog Out1 Sel = Output Freq.
(P343) Analog Out1 Hi = 10.0 V
(P344) Analog Out1 Lo = 0.0 V

10 14 15 22

+10 VDC

Analog In 1 (-)

Analog In 1 (+) Common

19

20

21

22

23

24

-

+

Com

mon

A O

ut V

olts

Control Wiring cont’d

Two Wire Start/Stop Control

(P89) Logic Source Sel = Terminal Block
(P361) Digital In1 Sel = Not Used
(P362) Digital In2 Sel = Run
(P363) Digital In3 Sel = Function Loss

Three Wire Start/Stop Control

(P89) Logic Source Sel = Terminal Block
(P361) Digital In1 Sel = Stop
(P362) Digital In2 Sel = Start
(P363) Digital In3 Sel = Function Loss

See Parameters P361 to P366 for
configuration of all logic inputs.

1 2 3 7 8 9

Run

Function Loss Supply Com.

Logic Com.

+24 VDC

1 2 3 7 8 9

Start

Function Loss Supply Com.

Logic Com.

+24 VDC

Stop

Power Wiring

Input Voltage: Determined by model
number. Voltage Class configures the
drive for International voltage supplies.

Control Wiring

Default:

(Out-of-the-box) configuration

is for Keypad control. The user will be
able to start the controller using the
built-in drive mounted operator interface
module.

3 7 8 9

Function Loss Supply Com.

Logic Com.

+24 VDC

Start
Stop

L1

R

L2

S

L3

T

+DC BRK T1

U

T2

V

T3

W

PE

PE

M

BR1 BR2

ATTENTION: The SP600 does
not provide branch circuit
protection. The user must install
the proper protection devices.

!