AN-T80016 Maintenance Override Programming

Issue 1 June 08

AN-T80016

7

Logic Chart

This table presents the logic in a similar way to Cause and Effect charts. It is recommended to analyse
the logic requirements of a function block before programming, because the resulting program will be
more reliable and robust to unusual combinations of inputs and internal states. List all inputs, all
previous values of inputs

Blank boxes in the table indicate ‘don’t care’ for that input.

OR

MC GOA MOE OS OA Timer

Implications

Action

F

Maintenance Override disable

Clear OS, zero/stop timer,clear
OA

F>T

T

T

Override requested and
enabled

Set OA, start timer

T>
T

F>T T

T

F

T

<30s

Override confirmed

Clear OA, set OS, zero/stop timer

F

Override cancelled

Clear OS, clear OA,zero/stop
timer

T

F

T

>30s

Override timer ran out

Clear OA, zero/stop timer

T

F

F

T

No group override available

Clear OA, zero/stop timer

The trip logic may be treated separately.

DI

RS

OS

T

T

Reset trip when input clear

Set DT

T

T

Reset trip when Override set

Set DT

F

F

Input tripped and no override

Clear DT