Status indicators, Configuration, Installation – Rockwell Automation T8293 Trusted Power Distribution Unit 15-Way Fused User Manual

Page 8: Associated trusted, Power cables

Advertising
background image

Trusted

TM

Power

Distribution Unit 15-Way Fused T8293

Issue 8 Jul 12

PD-T8293

8

Two 24V dc or 48V dc (link selectable) supplies, are distributed through 30 fuses, arranged in two
banks of 15 fuses. The outputs are fed via 15 terminal blocks labelled T1 to T7, and T11 to T18.

Each supply shares a common 0V reference.

Each fuse is monitored for open circuit condition and provides a local on-board LED indication of
individual fuse failure. Red LEDs are used to display the failed state.

A volt-free relay contact provides the fuse failure common alarm signal (contact open for fuse failure)
for connection to external alarm monitoring circuits.

2. Status Indicators

2-off green LED

On to indicate that the associated power supply feeder is healthy.

30-off red LED

On to indicate that the adjacent fuse has failed.

3. Configuration

Link selection for 24 or 48V dc operation. The appropriate link must be fitted to select the required
voltage.

4. Installation

The Trusted

TM

Power Distribution Unit 15-Way Fused may be mounted on either of the TS32 or TS35

DIN rails in the horizontal or vertical position as required.

5. Associated Trusted

TM

Power Cables

Cable Type

Description

TC-002-01

Interconnection Cable
MCB Distribution Unit (T8292) to Fuse Distribution Unit (T8293)

TC-003-01

Interconnecting Cable
Fuse Distribution Unit (T8293) to I/P FTAs

TC-004-01

Power Cable
Fuse Distribution Unit (T8293) to VFTA’s Single Power Group

Table 1 Associated Trusted

TM

Power Cables