Block diagram, Single channel schematic, Electrical specification – Rockwell Automation T8833 Trusted 20 Channel Analogue/Digital Isolated Input FTA User Manual

Page 2: Sds-8833 trusted, Industrial control system trusted

Advertising
background image

SDS-8833
Trusted

TM

Industrial Control System

Trusted

TM

20 Channel Analogue/Digital Isolated Input FTA - T8833

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

BLOCK DIAGRAM

Single Channel Schematic

ELECTRICAL SPECIFICATION

Field Current Loop (Per Channel)

2 to 30mA

Field Loop Volt Drop at 20mA

9.5V

Recommended Operating Current

2 to 20mA per channel

Power Consumption (Field Loop)

19mW maximum

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
120mm x 336mm x 50mm
(4.7ins x 13.2ins x 2 ins)

Weight (fully populated)
500gms
(1.1lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds

TB1 A

TB1 B

100R

7V5

CON1 VPOWER

CON1 COMMON

CON1 VSENSE

+

Advertising