Maintenance, Safety considerations – Rockwell Automation T8062 ICS Regent+Plus High Integrity Power Supply Assembly User Manual
Page 13
Advertising

I/O Power Supply Assembly (T8060,T8062)
P D - 6 0 5 0 M a r - 0 6
13
Triplicated 15 V Regent and 24 V N+1 Field Power
Maintenance
No periodic maintenance or calibration is required for I/O power supply
modules. There are no user-replaceable parts.
A failed I/O power supply module can be hot-replaced without disrupting
system operations. Main power wiring and I/O power cables (connected
to the chassis) are not disturbed during module replacement.
Safety Considerations
The power supply modules and chassis are TÜV certified for
Risk Class 5 safety critical applications.
Advertising
This manual is related to the following products: