Rockwell Automation 1440-TB-E XM-944 Process/Temperature Terminal Base User Manual
Page 21
XM-944 Process/Temperature Terminal Base 21
Publication
GMSI10-IN024A-EN-P - May 2010
XM-362 Isolated Thermocouple Temperature Module Terminal Assignments
No.
Description
No.
Description
0
Chassis ground
26
Channel 4 TC (-)
1
Chassis ground
27
Channel 5 TC (+)
2
Chassis ground
28
Channel 5 TC (-)
3
No connection
29
Channel 6 TC (+)
4
No connection
30
Channel 6 TC (-)
5
No connection
31
Channel 4 4-20mA (+)
6
No connection
32
Channel 5 4-20mA (+)
7
No connection
33
Channel 6 4-20mA (+)
8
No connection
34
Channel 1 4-20mA (-)
9
No connection
35
Channel 2 4-20mA (-)
10
No connection
36
Channel 3 4-20mA (-)
11
No connection
37
24V in
12
No connection
38
24V common
13
No connection
39
Reserved
14
No connection
40
No connection
15
Chassis ground
41
Chassis ground
16
Channel 1 4-20mA (+)
42
Chassis ground
17
Channel 2 4-20mA (+)
43
Chassis ground
18
Channel 3 4-20mA (+)
44
CAN_High (white wire)
19
Channel 1 TC (+)
45
CAN_Low (blue wire)
20
Channel 1 TC (-)
46
CAN Shield (bare wire)
21
Channel 2 TC (+)
47
DeviceNet V (+) (red wire) (Optional,
see IMPORTANT note below)
22
Channel 2 TC (-)
48
DeviceNet V (-) (black wire)
23
Channel 3 TC (+)
49
Channel 4 4-20mA (-)