Module status leds, Table 4 module status leds, Trusted – Rockwell Automation T8170 Trusted Gateway Module User Manual

Page 21: Module t8170

Advertising
background image

Trusted

TM

Module T8170

Issue 10 Apr 10

PD-8170

21

4.2. Module Status LEDs

There are ten status LEDs on the Gateway module front panel; one Healthy, one Active, one Standby,
one Educated, one Hard drive Active, one Status, and four Communications.

The module status LED states and their meanings are described as follows:

LED

INDICATION

Healthy

Module Health:
Steady green = Healthy, module self test has passed.
Steady red

= Faulty, module self test has failed.

Active

Unused, set steady green

Standby

Unused, set off.

Educated

Unused, set steady green

Communications

RS-232 serial port : The LED’s flash red when responding and green when
receiving and off if no activity.
Ethernet Ports: LED’s flash amber to indicate link activity and off if no activity.
Ethernet FP currently unused.

Disk

Flashing green when hard drive is active. Flashes red when secondary IDE is
in use.

Status

Reserved for future use.

Table 4 Module Status LEDs

Advertising