Fire Detector Input Modules (T7419)
 
P D - 7 0 3 2 M a r - 0 6  
19
Specifications
Safetybus Power
0.85 load units
Number of Inputs
16
Field Circuit Type
Standard 20 volt detector 
loop, line monitored and 
tested 
Field Power
Voltage:
Current:
15 to 40 VDC
1.2 amps, maximum
Nominal Operating Voltage
Module provides regulated 
23.5 Vdc for input loop 
End of Line Terminator
3.0 Kohm resistor, typical
Quiescent Current, 
Maximum 
3 to 10 mA, typical when 
detector in normal state 
Detector Alarm
See Load-line 
characteristics, page 9. 
Reset
Voltage:
Current:
Time
:
 
<1 volt 
<20 
m
A
Programmable
Test Interval
15 seconds (typical)
Intrinsic Safety
External barrier
Over voltage Protection
27 volts continuous, 500 
volts surge transient 
Fusing
None (internal current limit 
20 mA — no damage with 
continual short circuit or 
open input) 
Isolation
2500 volts minimum (field 
wiring to control logic) 
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)