Wire the devicenet network power supply – Rockwell Automation 1769-L24ER-QB1B_L24ER-QBFC1B_L27ERM-QBFC1B CompactLogix 5370 L2 Controllers Quick Start User Manual
Page 30

30
Rockwell Automation Publication IASIMP-QS025B-EN-P - December 2012
Chapter 1
Prepare the CompactLogix 5370 L2 Controller Hardware
Wire the DeviceNet Network Power Supply
1. Use the information in the following table to connect incoming power to the network
power supply.
2. Place the switch in the position that matches your supply voltage.
3. Use the information in the followingtable to connect the DeviceNet power tap to the
power supply.
4. Connect the DeviceNet power tap to the DeviceNet network.
5. Power the 1606- XLDNET4 standard switched-mode power supply connected to the
CompactLogix 5370 L2 controller, as described in
Connect Power to the Controller on
.
WARNING: Verify that all incoming power is turned off before wiring power.
Connect
To
V AC COM
N (neutral)
120/240V AC
L (line)
Ground
Connect
To
Red
+
White
N/A
Shield
N/A
Blue
N/A
Black
–
ATTENTION: If you have unused DeviceNet wires, make sure they do not come into contact with the other wires.