5. Specifications
Field Supply Range
18 to 32V dc
Maximum Normal Output Current I
sc
(Field
Supply)
81mA
Maximum Normal Output Voltage V
oc
(Field
Supply)
32V as voltage range above
Maximum External Capacitance C
a
5µF for methane, 0.3µF for groups A
and B, in accordance with AANSI/ISA
12.12.01-2000
Maximum External Inductance L
a
10mH for methane or group B, in
accordance with AANSI/ISA 12.12.01-
2000
Operating Temperature
-5° to 60°C (23°F to 140°F)
Non-operating Temperature
-25°C to 70°C (-13°F to 158°F)
Operating Humidity
5 to 95% RH
Environmental Specifications
Refer to Document 552517
Dimensions
Height
Width
Depth (including mounting rail and
connectors
)
110mm (4.44ins)
455mm (17.9ins)
68mm (2.67ins)
Weight
762gms (1.68lbs)