Figure 13 local and remote status table – Rockwell Automation AutoMax ControlNet Communication Interface Module User Manual
Page 52

Page 52 AutoMax ControlNet Module
Publication number DSMBCN-UM001B-EN-P February 2003
Code, hex Description
11
Destination memory full, cannot accept
command now
12
Destination did not acknowledge command
13
Network contention, possible duplicate node or
bad cabling
14
Local port is disconnected, or no other node
found
15
Timeout waiting for a reply message
16
Duplicate node detected
17
Node is offline
18 Hardware
fault
1D
Transaction number mismatch
1E
Duplicate transaction number
31
Illegal command or format
32
Host is malfunctioning and will not
communicate
33
Remote node host is missing, disconnected, or
shut down
34
Host could not complete function due to
hardware fault
35
Addressing problem or memory protected
rungs
36
Function disallowed due to command
protection selection
37
A-B Processor is in program mode
38
Compatibility mode file missing or
communication zone problem
39
Remote node cannot buffer command
3A (not
used)
3B
Remote node problem due to download
3C
Cannot execute command due to active IPBs
3D (not
used)
3E (not
used)
3F
There is an error code in the Extended Status
register (register 33 on the module). See
section 0.
Figure 13 Local and Remote Status Table