BLOCK DIAGRAM

ELECTRICAL SPECIFICATION

Number of Inputs

60 Channels

Field Common Isolation

Sustained Working

±250V dc

Maximum Withstanding

±2.5kV dc

Input Voltage

Measurement Range

±40V dc

Maximum Withstanding

±100V dc

Channel Input Resistance

5k9

Power Consumption

12 to 15W

Sample Update Interval (no filter)

5ms

Self-Test Interval

20s

Sequence of Events

Event Resolution

1ms

Time-stamp Accuracy

±0.5ms

Turn-on/off Voltage

Configurable

Fusing

None, external if required

Intrinsic Safety

External barrier

Circuit Type

Fault tolerant, 1-oo-2D with optional line
monitoring

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
241mm x 30mm x 300mm
(9.5ins x 1.2ins x 11.8ins)

Weight:
1.13kg
(2.5lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds