Rockwell Automation 34C473 General Purpose AC Drive DB Kit 5, 7-1/2, 10HP 3-Ph User Manual

Page 5

Advertising
background image

ADJUSTMENTS

DANGER

ADJUSTMENTS ARE MADE WITH POWER ON.

EXERCISE EXTREME CAUTION WHEN PERĆ

FORMING THESE ADJUSTMENTS AS HAZĆ

ARDOUS VOLTAGE EXISTS.

Dynamic braking action is automatic and is not adjustĆ

able. Current limit controls are provided for adjustment

of motoring and regenerative current.
1. Adjust both the Motoring Current Limit and the ReĆ

gen Current Limit potentiometers on the CLSA

Board to the approximate center of their ranges (12

o'clock position).

2. Adjust both the Accel Rate and the Decel Rate poĆ

tentiometers on the VSAA Board fully clockwise

(max rate) (Figure 4).

Setting the Motoring Current Limit
3. Turn the Speed Setting potentiometer on the OperĆ

ator's Control Station fully clockwise (max speed)

and press the Start rocker switch. If the rate of accelĆ

eration of the motor is as desired, the Motoring CurĆ

rent Limit is adjusted properly. If the acceleration

rate is not fast enough, go to Step 4; if too fast, go

to Step 5.

4. If the acceleration rate of the motor is not fast

enough, press the Stop rocker switch and allow the

motor to stop. Adjust the Motoring Current Limit

1/8th turn clockwise and, with the Speed Setting

potentiometer still at maximum speed, press the

Start rocker switch. Continue to repeat this proceĆ

dure until the desired acceleration rate is reached.
NOTE: If a point is reached where the drive shuts off

and coasts to a stop, the Motoring Current Limit has

been turned too far clockwise. (The Motoring CurĆ

rent Limit has exceeded the Instantaneous ElectronĆ

ic Trip [IET] current setting of the controller.) Reset

the drive by depressing the Stop rocker switch on

the Operator's Control Station. Then turn the MotorĆ

ing Current Limit a little counterclockwise and reĆ

peat the procedure described in Step 3.

5. If the acceleration rate of the motor is too fast, adjust

the Accel Rate potentiometer on the VSAA Board

about 1/4th turn counterclockwise and check the

acceleration according to Step 3. Continue to reĆ

peat this procedure until the desired acceleration

rate is reached.

Setting the Regen Current Limit

CAUTION: Should the regenerative current limit be

set below a particular motor's minimum current levĆ

el, the regenerative current limit circuitry may proĆ

hibit the motor from decelerating. Reset the regenĆ

erative current limit as described below.

6. Set the Speed Setting potentiometer on the OperaĆ

tor's Control Station fully clockwise (max speed)

and run the drive at maximum speed. Then quickly

turn the Speed Setting potentiometer fully counterĆ

clockwise (min speed). If the rate of deceleration of

the motor is as desired, the Regen Current Limit is

adjusted correctly. If the deceleration rate is too

long, go to Step 7; if too short, go to Step 8.
NOTE: The Regen Current Limit adjustment is not inĆ

tended to replace the Decel Rate adjustment on the

controller to provide long deceleration times.

7. If the deceleration rate of the motor is too long, inĆ

crease the Regen Current Limit adjustment 1/8th

turn clockwise and repeat the procedure described

in Step 6. Continue this procedure until the desired

deceleration time is reached.
NOTE: If a point is reached where the drive shuts off

and coasts to a stop, the Regen Current Limit has

been turned too far clockwise. (The Regen Current

Limit has exceeded the Instantaneous Electronic

Trip [IET] current setting of the controller.) Reset the

drive by depressing the Stop rocker switch on the

Operator's Control Station. Then turn the Regen

Current Limit a little counterclockwise and repeat

the procedure described in Step 6.

8. If the deceleration rate of the motor is too short, adĆ

just the Decel Rate potentiometer on the controller

about 1/4 turn counterclockwise and check the deĆ

celeration according to Step 6. Continue to repeat

this procedure until the desired deceleration is

reached.

Advertising