Rockwell Automation MDO16GNS 16-Channel Digital Output Module 48Vdc User Manual

Page 4

Advertising
background image

4

MDO16GNS October 2005 – Issue 2

Triguard SC300E

SPECIFICATION

Model

MDO16GNS

Channels

16

Architecture

TMR

Indicators:

Input

Modules

One per point
Health, 3 x On Line

Output driver

FET

Voltage range

48Vdc ±10%

Voltage drop

Less than 3V

Maximum drive

Resistive load: 1A per channel
Tungsten load: 0.125A per channel

Surge limiting

3A peak

Isolation

1kVdc field to system, commoned supply

Minimum load per output

12mA (24mA if dual slot hot repair)

Module power consumption excluding field
power dissipation in module

4W

Module power consumption including field
power dissipation in module

6W @ minimum load
36W @ maximum load

Overall size (mm)

Overall size (inches)

400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W

Weight

2.1kg

ENVIRONMENTAL SPECIFICATIONS

The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.

Temperature operating:

+5°C to +60°C

Temperature storage:

-25°C to +70°C

Humidity

5% to 95% non-condensing at ambient <40°C

EMC/RFI Immunity

Tested and certified to IEC 1131-Part 2 1994

Vibration/Shock

Tested and certified to IEC 1131-Part 2 1994

Certification:

General Certification: Ref. SC300E TMR Product Guide (ref 008-5209).