Block diagram, Electrical specification, Sds-8451 trusted – Rockwell Automation T8451 Trusted Industrial Control System User Manual
Page 2: Industrial control system trusted, Ics triplex, Mechanical specification, Environmental, Ofiu hiu fpdu fpiu, Oftu
 
SDS-8451 
Trusted
TM
Industrial Control System
Trusted
TM
TMR 24Vdc Digital Output Module-T8451
ICS Triplex 
 
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement. 
Specifications are subject to change 
without notice. For latest information, visit 
our Website:- 
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Number of Outputs
40 Channels
No. of Independent Power Groups
5, each of 8 outputs
Field Common Isolation
Sustained Working
±250V dc
Maximum Withstanding
±2.5kV dc
Output Voltage Field Supply
Measurement Range
0 to 36V dc
Maximum Withstanding
-1 to 60V dc
Output Current Rating
Continuous
2A
Output Off Resistance (effective 
leakage) 
33k=
Power Consumption (1A per channel 
)
24W
Output Turn On/Off Delay
0.5ms
Self-Test Internal
2 minutes
Output Short Circuit Protection
Automatic
Fusing
Not required
Intrinsic Safety
External barrier
Circuit Type
Fault tolerant, fully triplicated with 
optional line monitoring 
MECHANICAL 
SPECIFICATION 
 
Dimensions (HxWxD): 
241mm x 30mm x 300mm 
(9.5ins x 1.2ins x 11.8ins) 
 
Weight: 
1.13kg 
(2.5lbs) 
 
ENVIRONMENTAL
 
Operating Temperature: 
 
-5
°C to 60°C
(23
°F to 140°F)
 
Operating Humidity: 
5 to 95%, non-
condensing 
 
Vibration: 
10 to 57Hz 
±0.075mm
57 to 150Hz 1.0g 
 
Shock: 
15g, ½ sine wave, 11ms 
 
EMI (IEC 801): 
ESD 
Air discharge to 15kV 
Contact discharge to 8kV 
 
Radiated Fields 
10V/m, 27MHz to 
500MHz 
 
Transients and Bursts 
2kV, 2.5kHz for 
t=60 seconds 
Slice Power
Supply
Housekeeping
Failsafe Bias Control
A
Back Plane
Power Bus
1
Front Panel
T
M
R
In
te
rm
o
d
u
le
B
u
s
Opto Isolation Boundary
Serial Display Latches
Voted Status Display LEDs
Internal Voting Bus
Housekeeping
Module Temp
Supply Diag
DSP reference
Health
Indicators
Back Plane Power Bus 1
Back Plane Power Bus 2
Slice A
OFIU
HIU
FPDU
FPIU
Field Logic
Control
Redundant Supply
N.C.
N.O.
Diagnostic
Monitor
Bus
Interface
Bus
Interface
Slice Power
Supply
Housekeeping
Failsafe Bias Control
B
Field Logic
Control
N.C.
N.O.
Diagnostic
Monitor
Slice Power
Supply
Housekeeping
Failsafe Bias Control
C
Field Logic
Control
N.C.
N.O.
Diagnostic
Monitor
Bus
Interface
Front Panel
Voting Logic
Slice
Control
B
Time Stamp
Slice
Control
B
Time Stamp
Slice
Control
A
Time Stamp
OFTU
+V
Slice B
Slice C
A
B
C
Group
Fail-Safe
Switch
-
V
Field Interface
Protection Circuit