outputs, to operate load devices powered from isolated field 
power supplies. 
Each output is individually fused to protect the circuits from 
short circuit conditions in output wiring and field devices. 
Testing and Diagnostics
Each module’s voter circuits are periodically tested by the 
processor modules. Discrepant data are sent through one of 
three legs of the I/O Safetybus to determine whether the 
module’s voter is able to outvote the incorrect data. A failure 
to return the correct majority-voted result to the processors 
produces an I/O module error indication at the processor 
modules and a module fault indication at the I/O module. 
Each type of module has a unique identification code that is 
read by the controller. This code lets the controller know 
which type of module is installed in each I/O chassis slot and 
how to address that module and its points specifically. If a 
module is removed, or is replaced with a module of a different 
type, the processor modules will indicate an I/O module error. 
Loopback logic tests periodically write data to the module and 
then read it back to determine whether the module’s I/O bus 
interface logic is functioning correctly. 
Fuses are continually checked for continuity. Field power and 
the minimum load (see Specifications, page 12) must be 
connected to each output in order to detect a blown fuse. 
Front Panel Indicators
The 110 VAC isolated digital output module is shown in 
Figure 2. The front panel contains the active and fault status 
indicators, shutdown indicator, and output status and blown 
fuse indicators for each output circuit. 
Active and Fault Status Indicators
These green and red LEDs indicate the overall health of the 
module. During normal operation, the green ACTIVE 
indicator flashes at the controller’s scan rate. If a module 
fault is detected the red FAULT indicator turns on and the 
green indicator turns off.