Block diagram, Electrical specification, Sds-8017 trusted – Rockwell Automation T8017 Trusted Peer to Peer Communications User Manual
Page 2: Industrial control system trusted, Peer to peer communications - t8017
 
SDS-8017 
Trusted
TM
Industrial Control System
Trusted
TM
Peer to Peer Communications - T8017
ICS Triplex 
 
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement. 
Specifications are subject to change 
without notice. For latest information, visit 
our Website:- 
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
No. of Peer Networks per 
System 
<4
Target Inter-application 
Response 
Single point change
nx15ms + 2x(source + destination 
application scan) 
All points change
nx15ms + (per 1000 digital points per 
node) +nx15ms + (per 60 analogue 
points per node) +2x(source 
+destination application scan) 
n=no. of nodes/systems on the network
Points per Network
40000 digital 
20000 analogue 
No. of Nodes per Network
2<n<10
Points per node/System
Peer Communication points are to be 
included in the total number of external 
points. Each point is equivalent to a 
single I/O point. The total I/O point 
count must remain within the Trusted
TM
IEC1131 TOOLSET constraints.
MECHANICAL, 
ELECTRICAL AND 
ENVIRONMENTAL 
SPSECIFICATION 
 
The Peer to Peer 
Communications employs 
the Trusted
TM
Communications Interface. 
Refer to the corresponding 
product information for 
further details of the 
electrical, mechanical and 
environmental 
specifications. 
Error! Objects cannot be created from editing field codes.