Specifications – Rockwell Automation T3419 ICS Regent Fire Detector Input User Manual

Page 20

Advertising
background image

Fire Detector Input Modules (T3419)


2 0

Industrial Control Services

Specifications

Safetybus Power

0.85 load units

Number of Inputs

16

Field Circuit Type

Standard 20 volt detector
loop, line monitored and
tested

Field Power

Voltage:

Current:

15 to 40 VDC

1.2 amps, maximum

Nominal Operating Voltage

Module provides regulated
23.5 Vdc for input loop

End of Line Terminator

3.0 Kohm resistor, typical

Quiescent Current,
Maximum

3 to 10 mA, typical when
detector in normal state

Detector Alarm

See Load-line
characteristics, page 10.

Reset

Voltage:

Current:

Time

:


<1 volt
<20

m

A

Programmable

Test Interval

15 seconds (typical)

Intrinsic Safety

External barrier

Over voltage Protection

27 volts continuous, 500
volts surge transient

Fusing

None (internal current limit
20 mA — no damage with
continual short circuit or
open input)

Isolation

2500 volts minimum (field
wiring to control logic)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Advertising