Assembly layout, Electrical specification, Sds-824x trusted – Rockwell Automation T824X Trusted Power System User Manual
Page 2: Industrial control system trusted, Power system-t824x
 
SDS-824X 
Trusted
TM
Industrial Control System
Trusted
TM
Power system-T824X
ICS Triplex 
 
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement. 
Specifications are subject to change 
without notice. For latest information, visit 
our Website:- 
www.icstriplex.com
ASSEMBLY LAYOUT 
ELECTRICAL SPECIFICATION 
Voltage Range – Input
90V ac to 264V ac
Voltage Range – Output
24Vdc or 28V dc (23-28 adjustable)
Frequency Range
47Hz to 63Hz
Inrush Current
50A max
Power Factor
0.95 min, 0.99 typical
Efficiency
78 – 84%
Hold-up Time
20ms min
Output Power
750W per Power Pack
Isolation voltage
3kVac, Primary to secondary 
1.5kVac Primary or secondary to ground 
MECHANICAL 
SPECIFICATION 
 
Dimensions (HxWxD): 
43.5mm x 483mm x 
340mm 
(1.71ins x 19ins x 
13.36ins) 
Note: Optional support 
bracket requires minimum 
4U rack height. Unused 
space may be populated 
by other equipment. 
 
Weight (fully populated) 
10kg (approx.) 
22lbs (approx.) 
 
ENVIRONMENTAL
 
Operating Temperature: 
0
°C to 60°C
(30
°F to 140°F)
 
Operating Humidity: 
5 to 95%, non-
condensing 
 
Vibration: 
10 to 57Hz 
±0.075mm
57 to 150Hz 1g 
 
Shock: 
15g, ½ sine wave, 11ms 
 
EMI (IEC 801): 
ESD 
Air discharge to 15kV 
Contact discharge to 8kV 
 
Radiated Fields 
10V/m, 27MHz to 
500MHz 
 
Transients and Bursts 
2kV, 2.5kHz for 
t=60 seconds