Rockwell Automation MHB44IND Pulse Input and Analogue Output Module User Manual
Page 4

4
MHB44IND October 2005 – Issue 2
Triguard SC300E
SPECIFICATION
Model
MHB44IND
Channels
4 x pulse inputs
4 x analogue outputs
Architecture
TMR
Indicators
Health, 3 x On Line
Test Point
4 x signal, 1 x common
Output range
0 to 22mA
Maximum resistive field load
400ohm
Resolution
6.25
µ
A steps
Accuracy @ @ 25°C
+0.2% of full signal range
Maximum input ripple voltage @24V field
supply
12V peak to peak
Maximum input ripple frequency
120Hz
Stability (temperature coefficient)
15ppm/°C
Isolation
1kV to system, commoned supply
Field power supply:
Voltage range
+18Vdc to 30Vdc
Module power consumption
5.5W
Pulse input waveform
Sine/Square/Pulse
Pulse input amplitude
100mV to 132V peak
(NOTE: For sinewave inputs less than 10Hz
amplitude minimum rises linearly to 200mV at
1Hz)
Pulse input duty cycle
10 to 90% up to 3.5kHz
Pulse input width (minimum)
14ms above 3.5kHz
Pulse input impedance
10k ohm
Pulse input frequency resolution
16 bits
Pulse input frequency accuracy
± 0.01% 1Hz to 35kHz
Overall size (mm)
Overall size (inches)
400(9U)H x 397L x 28W
15.75H x 15.63L x 1.1W
Weight
1.7kg