1. Description

The Trusted

TM

40 Channel Analogue Input FTA T8830 provides termination for a maximum of 40 input

channels from various types of field devices which generate an analogue input. Figure 2 below shows
the configuration of a single channel.

Figure 2 Single Channel Schematic

The supply for the field is derived from dual 24V dc feeds which are ‘commoned’ via diodes on the
FTA. Indication of the presence of the power supply is provided by a green LED. The supply is then
fed to each channel.

The supply voltage to the field is fed via the 50mA fuse. This effectively limits the current in the field
loop. The voltage developed across the 250R resistor due to the incoming analogue signal from the
field device is fed directly to the analogue input module.

The cable linking the 40 channels on the input module to the FTA is terminated at the 96-way socket
SK1. SmartSlot (Version 1) signals from the module are connected to SK1. The SmartSlot connector
is SK2 and is also a 96-way socket. This connector is not used where SmartSlot Version 2 is
employed within the Trusted

TM

System. The dual dc field power supplies are connected to the FTA via

a 5-way terminal block PWR TB. The input signals from the field (40-off) are connected by 2-wire
arrangements terminated on 12-off 3-way terminal blocks and 2-off 2-way.