MDO16FNS October 2005 – Issue 4

Triguard SC300E

SERVICING

SCOPE

Repair is by module replacement. Faulty modules are not repairable in the field. They should
be replaced by new modules and returned for repair.

WARNING

Lethal voltages are present in this equipment.

The protective covers are to prevent access to circuits. There are no user-serviceable

components under the covers

For your safety:

Do not remove the covers.

Do not touch any exposed circuits or insert objects such as test probes through the covers

while the module is connected to the chassis backplane.

CAUTION 1

Before fitting a new module ensure that the setting of all three links is the same as that on the
old module.

CAUTION 2

This module contains components that may be electrostatically sensitive. It should be
transported and stored in its original packaging material.

DIAGNOSIS

The TriBuild workstation is used for fault diagnosis. In the case of an Input/Output fault the
Health LED on the faulty module will be extinguished.

PREPARATION

To ascertain whether the chassis I/O slot containing the faulty module has been allocated a
hot repair partner, use one of the following methods:

Check the system drawings

Check the chassis wiring configuration

Use the I/O chassis Configuration Report on the TriBuild workstation.