(1) The bezel’s lower DPI port is always Port 2, and the cradle connection port is always Port 3.
For the drive to receive its speed reference from:
•
The OIM in the bezel, set parameter Speed Ref A Sel (90) or Speed Ref B Sel (93), depending on your
application requirements, to “20” (DPI Port 3).
•
A remote OIM connected directly into Port 2 on the bottom of the drive, set parameter Speed Ref A Sel (90) or
parameter Speed Ref B Sel (93) to “19” (DPI Port 2).
No.
Connector
Port ID
Description
➊
Internal Connection
--
Connects the REBZL-N1 Bezel Kit to the drive.
➋
Lower DPI Port
(1)
Port 2
Connects a RECOMM-232 or RECOMM-USB converter to
the drive.
➌
Cradle Connection
(1)
Port 3
Connects the OIM to the bezel.