TAI16AIR October 2005 – Issue 5

Triguard SC300E

Model

TAI16AIR

Maximum field supply voltage

33Vdc

Current rating

50mA per channel

Fuse in each positive line to field

1A, fast acting, indicating

Fuse in each negative line to field

63mA, fast acting

Terminating resistor

250 ohm, 0.5W, 0.1% high stability, 3ppm/°C

Chassis cable connector

34 way DIN41612

Field cable connector

Screw terminal to suit 2.5mm

2

wire (16 AWG)

Fuse blown indication

Local: Fuse blown LED (one per card)

Remote: Fuse blown alarm output (PL1) – can
be connected to Fuse blown LED on Power
Distribution Panel (PDD24).

Transient suppression

A transient suppressor clamps the voltage
across each input pair as follows (the device
is bi-directional):

14Vdc to 17Vdc @ 1mA (max current for
continuous overload)

27Vdc @ 176A max peak pulse current for 8
to 20Bs

Safety ground terminal TS1

M3 threaded bush provision for a ring terminal.
Allows the common 0V supply bus to be
grounded via a 10k ohm resistor. Prevents the
channels from ‘floating’ when the I/O module
is removed from the chassis.

Overall size (mm)

Overall size (inches)

162L x 125W x 107H

6.4L x 4.9W x 4.2H

Weight

0.36kg