Rockwell Automation T8311 Trusted TMR Expander Interface User Manual
Sds-8311 trusted, Industrial control system trusted, Tmr expander interface-t8311
 
SDS-8311 
Trusted
TM
Industrial Control System
Trusted
TM
TMR Expander Interface-T8311
Issue 5 Jan 2006
FRONT PANEL
T
83
11
T
ru
st
ed
E
xp
an
d
er
In
te
rf
ac
e
Healthy
Active
Standby
DESCRIPTION
 
The Trusted
TM
TMR Expander Interface
module resides in the Trusted
TM
Controller
Chassis and provides the ‘master’ interface 
between the Inter-Module Bus (IMB) in the 
Controller Chassis and the Expander Bus. The 
Expander Bus allows multiple chassis systems 
to be implemented using UTP cable 
connections whilst maintaining the fault 
tolerant, high bandwidth IMB capabilities. 
The module provides fault containment 
for the Expander Bus, the module itself 
and the IMB in the Controller Chassis, 
ensuring that the effects of these 
potential faults are localised and system 
availability maximised. The module is 
fault 
tolerant
with
Hardware
Implemented Fault Tolerant (HIFT), 
Triple 
Modular
Redundant
(TMR)
architecture.
Comprehensive
diagnostics, monitoring and testing 
provide rapid fault identification. Hot 
standby 
and
module
sparing
configurations are supported, allowing 
automatic and manual repair strategies. 
Communication between the Expander 
Interface and the TMR Processor is via 
the IMB on the backplane of the 
Controller Chassis. The IMB provides 
fault tolerance and high bandwidth 
communications between the Interface 
Modules and the TMR Processor. All 
transactions are voted, localising faults 
to a Fault Containment Region (FCR) 
within the IMB should they occur. 
Communication between the Interface 
Module and the TMR Expander 
Processor in the Expander Chassis is 
via the Expander Bus. The Expander 
Bus 
is
triplicated,
point-to-point
architecture. Each channel of the 
Expander Bus comprises separate 
command and response media. Voting 
is provided at the Expander Bus 
Interface to ensure that cable faults are 
tolerated, and the remainder of the 
Expander Processor operates in a fully 
triplicated mode, even in case of cable 
faults occurring. 
The TMR Expander Interface Module 
derives its internal voltages from dual 
redundant +24V dc power supplied via 
the 
module
connector
from
the
Trusted
TM
Controller
Chassis
backplane. Each FCR derives the 
required supplies independently. 
Non-critical monitoring and module 
status display functions (front panel 
LEDs) are also provided. 
FEATURES
Triple Modular 
Redundant (TMR) 
fault tolerant (3-2-0) 
operation 
Hardware 
Implemented Fault 
Tolerant (HIFT) 
architecture 
Dedicated hardware 
and software test 
regimes which 
provide fast fault 
recognition and 
response times 
Automatic fault 
handling without 
nuisance alarming 
Hot replaceable
Front panel status 
LEDs