Rockwell Automation 1305 RFI Filter PLUS,PLUSII,FORCE,IMPACT Installation User Manual
Page 14
![background image](/manuals/581448/14/background.png)
12
Input RFI Filters
Filter Mounting
(continued)
1
Input power (source to filter) and output power (filter to drive and drive to motor) wiring must be in conduit or have shielding/armor with equivalent attenuation. Shielding/
armor must be bonded to the metal bottom plate.
2
Refer to the Filter Selection table on page 5 for frame references and corresponding catalog numbers.
Conduit Box
1
To Motor
1
Access Panel and
Input Terminal Block
Lower Access Panel
Important: Drive and filter must be mounted
to a common back plane with a positive
electrical bond. Spacing is determined by
Conduit Box.
Three-Phase
Input
1
To Motor
1
Three-Phase
Input
1
Conduit Box
1
Nipple/Fitting
Figure 3
1336 PLUS,
PLUS
II
,
FORCE & IMPACT
(Through-the-Wall Mounting)
Frames D & E
2
Figure 4
1336 PLUS,
PLUS
II
,
FORCE & IMPACT
(Conventional Mounting)
Frames D & E
2