Block diagram, Electrical specification, Sds-8290 trusted – Rockwell Automation T8290 Trusted Output Power Distribution Unit User Manual
Page 2: Industrial control system trusted, Output power distribution unit-t8290
 
SDS-8290 
Trusted
TM
Industrial Control System
Trusted
TM
Output Power Distribution Unit-T8290
ICS Triplex 
 
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement. 
Specifications are subject to change 
without notice. For latest information, visit 
our Website:- 
www.icstriplex.com
BLOCK DIAGRAM
ELECTRICAL SPECIFICATION
Voltage Range
0 to 140V dc
Supply Current
60A max
Supply Connection +ve
2-off M6 x 25mm studs
0V Reference Connector (not 0V 
return) 
BLZ 2-part terminal
Power Output (3-off)
6-way AMP MATE-N-LOK connector
0V Reference Connector (3-off)
5-way BLZ 2-part terminal
Conductor Clamping Range
0.5 to 2.5mm
2
MECHANICAL 
SPECIFICATION 
 
Dimensions (HxWxD): 
70mm x 90mm x 50mm 
(2.75ins x 3.54ins x 
1.97ins) 
 
Weight (fully populated) 
106gms 
(0.23lbs) 
 
ENVIRONMENTAL
 
Operating Temperature: 
 
-5
°C to 60°C
(23
°F to 140°F)
 
Operating Humidity: 
5 to 95%, non-
condensing 
 
Vibration: 
10 to 57Hz 
±0.075mm
57 to 150Hz 1.0g 
 
Shock: 
15g, ½ sine wave, 11ms 
 
EMI (IEC 801): 
ESD 
Air discharge to 15kV. 
Contact discharge to 8kV 
 
Radiated Fields 
10V/m, 27MHz to 
500MHz 
 
Transients and Bursts 
2kV, 2.5kHz for 
t=60 seconds