Rockwell Automation 440R CU2 Stop Motion Detector User Manual

Stop motion detector, Technical specifications, Bc d

Advertising
background image

To gain access
to switches & fuse
flip off lid with
a small screwdriver.

Access to replaceable fuse

Isolate power
before opening.

Technical Specifications

CU2

STOP MOTION DETECTOR

TERMINAL CONNECTIONS

120

35mm DIN rail
mounting

45

73

Power supply:

Relay outputs:

Maximum switched:

current/voltage/load

Internal fuse:

Mounting:

Enclosure protection:

Terminal Isolation:

Ambient temperature:

Internal switches:

LED indication:

Standards conformity:

110/230V AC (Switch selectable)
or 24V AC/DC
2 N/O + 1N/C (TUV approved)
4A/250V AC/1000VA
2A/30V DC/60W
500mAT (replaceable)
35mm DIN Rail
IP 40 DIN 0470
IP 20 DIN 0470
-10

°

C to +55

°

C

110/230V AC selector
A, B, C, D timing range selector
Red = Power On
Red/Green LED : Red = Timing,
Green = Output
EN 60204, BS EN 292

SUPPLY

110/230

V AC

SELECTABLE

OR

24VAC/DC

13

23

31

14

24

32

A1

Y1

Y2

A2

TEST

SAFETY

1

SAFETY

2

AUXILIARY

TIMER RANGE INTERNAL SWITCH SETTING

The CU2 provides a stopped motion detection system and is used together with CU2 sensors
to detect movement of a machine via the flywheel, gear or shaft etc. Upon energisation the
unit powers up (Red LED). When the sensor detects that the machine has stopped the CU2
integral timer operates and after the selected time delay the Signal LED turns Green. This
indicates that the safety outputs are closed and the CU2 will allow access to the machine,
typically via a solenoid operated guard interlocking switch with guard locking. In this way the
machine is at an ensured stop before access is possible. The auxiliary output is now "OFF".
The outputs and timer circuit are failsafe and cross monitored.
Time delay selection is a simple matter for a qualified person to set the DIP switches and fine
tune accordingly. In addition a replaceable plug-in 500mAT fuse is accessible behind the
removable panel (isolate the power before opening) preventing short circuits or overloads
from damaging the unit. Terminals YI - Y2 can be used to provide monitoring of the contactors
at power up of the CU2.

CU2 TIMER UNIT

CU2 SENSOR (2 REQUIRED)

500mA

Check time delay is set correctly

3

2

Fine tune

1 2

1 2

1 2

1 2

< 1 second to 10 seconds.

A

1 second to 39 seconds.

6 second to 5 mins 10 seconds.

48 second to 41 mins

B

C

D

1

Select general range

SUPPLY

SUPPLY

K1

K2

K1

K2

M

STOP

K1

K2

START

SOLENOID

LOCKING

SWITCH

A1

Y1

P

P

N

P

N

N

Y2

A2

14

13

NPN

INDUCTIVE

SENSOR

PNP

INDUCTIVE

SENSOR

NPN INDUCTIVE SENSOR

PNP INDUCTIVE SENSOR

L1 L2 L3

POWER

OUTPUT

MADE IN THE EC

Sicherheitstechnik

CU 2

EN60204
BS EN 292

A2 P N P Y2 14 24 32

A1 N P N Y1 13 23 31

SUPPLY

SUPPLY

Stop Motion Detection

BROWN BLACK BLUE

BROWN BLACK

BLUE

M18

80

Ø16

DIMENSIONS

Minimum

Maximum

SOLENOID

SAFETY CONTACTS

6mm

max

6mm

max

LOCKTITE

THREADS

*

*

SENSOR INSTALLATION

Each sensor must have a separate
mounting bracket (not supplied)

Rotary movement

of machine

Part No: 70884