Electrical specification, Sds-t8840 trusted, Industrial control system trusted – Rockwell Automation T8840 Trusted Temperature Input FTA User Manual

Page 2: Temperature input fta - t8840

Advertising
background image

SDS-T8840
Trusted

TM

Industrial Control System

Trusted

TM

Temperature Input FTA - T8840

ICS Triplex

Technical data sheets are intended for
information and guidance. The Company
has a policy of continual product
development and improvement.
Specifications are subject to change
without notice. For latest information, visit
our Website:-

www.icstriplex.com

ELECTRICAL SPECIFICATION

Voltage Range

15 to 28V dc

Maximum Input Current

2.5A

Number of Inputs

8

Possible Input Types

Isolated Voltage

(dependant on conditioning unit
fitted)

Isolated Current

Isolated RTD Pt 100ohm

Isolated RTD Ni 120ohm

Powered Isolated 2 wire 4-20mA
transmitter

Isolated Potentiometer

Isolated Thermocouple J,K

Accuracy, resolution

Dependant on conditioning unit

MECHANICAL
SPECIFICATION


Dimensions (HxWxD):
110mm x 145mm x 68mm
(4.3ins x 5.7ins x 2.6ins)

Depth with conditioning
unit fitted:
90mm
(3.6ins)

Weight (fully populated)
248gms
(0.55lbs)

ENVIRONMENTAL


Operating Temperature:

-5

°C to 60°C

(23

°F to 140°F)


Operating Humidity:
5 to 95%, non-
condensing

Vibration:
10 to 57Hz

±0.075mm

57 to 150Hz 1.0g

Shock:
15g, ½ sine wave, 11ms

EMI (IEC 801):
ESD
Air discharge to 15kV.
Contact discharge to 8kV

Radiated Fields
10V/m, 27MHz to
500MHz

Transients and Bursts
2kV, 2.5kHz for
t=60 seconds

Advertising