(T3444) AC Digital Output Module


P D - 6 0 1 6 M a r - 0 6

13

Specifications

Safetybus Power

0.8 load units

Number of Outputs

16 circuits divided into two
groups of 8 circuits each

Voltage Range

90 to 130 VAC

Frequency Range

47 to 63 Hz

Load Current

2 amps maximum per output
0

°

to 50

°

C, derated linearly

to 1 amp at 60

°

C

8 amps maximum per group
of 8 outputs 0

°

to 60

°

C

16 amps maximum per
module 0

°

to 60

°

C

Minimum Load

50 mA

On State Drop

2.0 volts maximum

Surge Current

15 amps, 20 msec

Output Leakage

5 mA maximum

Fusing

One 3 A, 250 V, fast-acting
(3AG) per output, front panel
mounted

Turn-On Delay

½ AC cycle, maximum

Turn-Off Delay

½ AC cycle, maximum

Heat Dissipation

28 Watts, 97 BTUs/hour

Over voltage Protection

175 VAC, continuous

Isolation

2500 volts minimum (field
wiring to control logic)
2500 volts minimum (output
group 1-8 to output group 9-
16)

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)