P.039 encoder loss enable – Rockwell Automation GV3000/SE 230VAC 30-100HP GP & Vector Drive V6.04 Start-Up and Reference Manual User Manual
Page 120

4-34
GV3000/SE 230 VAC Drive, Software Reference Version 6.04
Figure 4.6 - Typical Preset Operation
P.031 to P.038 Preset Speed 1 Through Preset Speed 8
(continued)
P.038
P.037
P.036
P.035
P.034
P.033
P.032
P.031
Preset 1
(or TS
Analog in)
Digital In 6
(Term. 19)
Digital In 7
(Term. 18)
Digital In 8
(Term. 17)
Run and Start
Closed
Closed
Closed
Closed
Closed
Closed
Closed
Closed
P.039 Encoder Loss Enable
This parameter
enables the encoder
loss detection
diagnostic.
This diagnostic is
available for flux
vector control (FVC)
only.
Parameter Range:
OFF = Disable encoder loss diagnostic
ON = Enable encoder loss diagnostic
Default Setting:
OFF
Parameter Type:
Tunable
Refer also to parameters: N/A
The encoder loss detection diagnostic is functional only when the drive is operating
as a speed regulator (not as a torque regulator).
When the diagnostic is enabled and feedback from the encoder is not detected, a
drive fault will be logged (EL will be displayed).
If the encoder fails, loss will be detected down to 1 RPM. If only one of the
quadrature feedback wires is disconnected, loss may not be detected below 15
RPM.