Block diagram, Single channel schematic, Electrical specification – Rockwell Automation T8802 Trusted 60 Channel 24V dc Digital Input FTA User Manual
Page 2: Sds-8802 trusted, Industrial control system trusted
 
SDS-8802 
Trusted
TM
Industrial Control System
Trusted
TM
60 Channel 24V dc Digital Input FTA - T8802
ICS Triplex
Technical data sheets are intended for 
information and guidance. The Company 
has a policy of continual product 
development and improvement. 
Specifications are subject to change 
without notice. For latest information, visit 
our Website:- 
www.icstriplex.com
BLOCK DIAGRAM
Single Channel Schematic
ELECTRICAL SPECIFICATION
Voltage Range (Field Supply)
18 to 28V dc
Fuses
61-off 50mA
Maximum Current (Field Supply)
3A
Recommended Operating Current
6.4mA per channel maximum
Power Consumption (Field Supply)
10W maximum
MECHANICAL 
SPECIFICATION 
 
Dimensions (HxWxD): 
110mm x 455mm x 68mm 
(4.3ins x 17.9ins x 2.6ins) 
 
Weight (fully populated) 
762gms 
(1.68lbs) 
 
ENVIRONMENTAL
 
Operating Temperature: 
 
-5
°C to 60°C
(23
°F to 140°F)
 
Operating Humidity: 
5 to 95%, non-
condensing 
 
Vibration: 
10 to 57Hz 
±0.075mm
57 to 150Hz 1.0g 
 
Shock: 
15g, ½ sine wave, 11ms 
 
EMI (IEC 801): 
ESD 
Air discharge to 15kV. 
Contact discharge to 8kV 
 
Radiated Fields 
10V/m, 27MHz to 
500MHz 
 
Transients and Bursts 
2kV, 2.5kHz for 
t=60 seconds