Specifications, Trusted – Rockwell Automation T8801 Trusted 40 Channel 24V dc Digital Input FTA Non Incendive User Manual

Page 12

Advertising
background image

Trusted

TM

24Vdc Digital Input FTA T8801

Issue 7 Jul 12

PD-T8801

12

5. Specifications

Voltage Range

18 to 32V dc (not 48VDC)

Maximum Normal Output Current I

sc

(Field

Supply)

12mA

Maximum Normal Output Voltage V

oc

(Field

Supply)

32V as voltage range above

Maximum External Capacitance C

a

5µF for methane, 0.3µF for groups
A and B, in accordance with
AANSI/ISA 12.12.01-2000

Maximum External Inductance L

a

100mH for methane or group B, in
accordance with AANSI/ISA
12.12.01-2000

Operating Temperature

-5

0

C to 60

0

C (23

0

F to 140

0

F)

Non-operating Temperature

-25

0

C to 70

0

C (-13

0

F to 158

0

F)

Operating Humidity

5 to 95% RH non-condensing.

Environmental Specifications

Refer to Document 552517

Dimensions

Height

Width

Depth


111mm (4.4ins)
335mm (13.2ins)
51mm (2ins)

Weight

900gms (2lbs)