Rockwell Automation 1440-TB-G XM-946 EODS Relay Terminal Base User Manual
Page 15

XM-946 EODS Relay Terminal Base 15
Publication
GMSI10-IN017A-EN-P - May 2010
Terminal Assignments
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been removed
or the area is known to be nonhazardous.
Do not disconnect connections to this equipment unless power
has been removed or the area is known to be nonhazardous.
Secure any external connections that mate to this equipment by
using screws, sliding latches, threaded connectors, or other
means provided with this product.
ATTENTION
The terminal block assignments are different for different
terminal base units. The following table applies only to the
XM-946. Refer to the installation instructions for the specific
terminal base unit for its terminal assignments.
IMPORTANT
The primary 24V dc needs to be wired to terminal 0 to
provide power to XM-946 and other XM modules located on
the DIN rail. Terminal 3 should be used if a second, or
redundant, power supply is needed. Note that terminal 3
provides redundant power only to the XM-946. It does not
serve other terminal base units.
No.
Description
No.
Description
0
24V in 1
26
No connection
1
24V common
27
Shutdown relay 3 common contact 1
2
Reset relay
28
Alarm relay common contact 2
3
24V in 2
29
Alarm relay common contact 1
4
Shutdown relay 1 N.O. contact 2
30
No connection
5
Shutdown relay 1 N.O. contact 1
31
Chassis ground
6
Shutdown relay 2 N.O. contact 2
32
No connection
7
No connection
33
No connection