Rack 3: ai, Table 7 rack 2: state output descriptions, Table 8 rack 3: ai descriptions – Rockwell Automation T8461 Trusted TMR 24 48Vdc Digital Output Module User Manual

Page 20: Trusted, Module t8461

Advertising
background image

Trusted

TM

Module T8461

Issue 13 Apr 10

PD-T8461

20

Value

Description

7

Channel fault

6

Field fault (e.g. field leakage to 0V or 24V)

5

Short circuit in field wiring or load

4

Output energised (ON)

3

Open circuit in field wiring or load

2

Output de-energised (OFF)

1

No field supply voltage

0

Unused

Table 7 Rack 2: State Output descriptions

3.2.3. Rack 3: AI

The AI board returns the field loop voltage at the output.

Channel

Description

1

Field output channel 1 voltage

2

Field output channel 2 voltage

40

Field output channel 40 voltage

Table 8 Rack 3: AI descriptions

The voltage is the median value taken from the triplicated module. The voltage level is reported as an
integer, with the units being

1

/

500

V. This may be used directly, scaled arithmetically or scaled using the

IEC1131 TOOLSET conversion tables.

To scale the value arithmetically simply divide the returned ‘integer’ by 500 to return the voltage as
either a REAL or INTEGER as required.

The IEC1131 TOOLSET conversion tables may be used to convert the value to engineering units, in
this case voltage. The full-scale range for this number format is decimal ±64, corresponding to
physical range –32000 to +32000.