Rockwell Automation T8433 Trusted TMR Isolated Analogue Input Module User Manual

Sds-8433, Trusted, Industrial control system trusted

Advertising
background image

SDS-8433

Trusted

TM

Industrial Control System

Trusted

TM

TMR Isolated Analogue Input Module-T8433

Issue 3 Aug 2006

FRONT PANEL

DESCRIPTION


The

Trusted

TM

TMR

Isolated

Analogue Input module interfaces to
20 single-ended or differential
current loop transmitters. The
module is normally used with the
T8833 FTA, which provides power to
the isolated input circuits from the
field loop. The module may also be
used for many other current loop
configurations.

Comprehensive

diagnostic tests are performed on
each input channel, including tests
for out of range values and stuck at
failures.

Fault tolerance is achieved through
Triple Modular Redundancy (TMR)
within the same module for each of
the 20 input channels.

The module can apply a digital filter
to each input channel. Individual
channels can be configured for high
noise immunity (50Hz or 60Hz
rejection), low noise immunity (fast
response),

or

pass-through

operation (no filtering).

Each input channel has four
configurable state thresholds, which
may be assigned to SOE reporting.
A change of state triggers an SOE
entry. The on-board Sequence of
Events (SOE) reporting has a
resolution of 1ms.

Each triplicated section of the
module, referred to as a slice,
conditions and measures each
channel independently. Each slice
is opto-isolated up to 2500V dc.
Each slice sends its data to a safety
layer hardware voter that presents
the information from all three slices
to the Trusted

TM

TMR Processor.

When a fault is detected on a slice
of the module, the Trusted

TM

TMR

Processor will flag the error,
indicating the need to replace the
module. The Trusted

TM

TMR

Processor will continue to use the
information

provided

by

the

remaining two slices until a
replacement module is available.
Replacement modules can be
located in a standby slot next to the
module or in a designated SmartSlot
with a temporary connection to the
same

Trusted

TM

Termination

Assembly.

Modules may be placed in any I/O
module

slot

in

a

Trusted

TM

Processor Chassis or Expander
chassis. Once the I/O module
configuration is set, mechanical
keying is available on all I/O
modules to prevent inserting a
module into an incorrect slot.

Configuration of the module is
carried out using the Trusted

TM

Toolset running on an Engineering
Workstation. Once configured and
loaded into the Trusted

TM

Controller,

replacement modules are on-line
educated by the TMR Processor.


FEATURES

20 TMR isolated input
channels per module

Comprehensive diagnostics
and self-test

2500V dc Opto-Isolation

Digital signal filtering on a per
channel basis

Four user configurable
thresholds per channel

On-board 1ms resolution
Sequence of Events reporting

Hot replaceable

Front panel status LEDs for
each channel

Module fault and status
indicators

IEC 61508, SIL 3 safety
applications

Advertising