Rockwell Automation DeviceNet KwikLink Configuration Drawing with Notes User Manual

Devicenet kwiklink lite popular configuration, Parts catalog table

Advertising
background image

DeviceNet KwikLink Lite Popular Configuration

Note: Performance is what we tested,

not the max capacity

1

2

3

4

2

1

3

4

B

B

A

A

Red

24 VDC

White

CAN_H

Blue

CAN_L

Black

0V DC

V+

V-

Valve Bank

1799-ZC10V

Stack Lights

Stack Lights

Series 9000

Sensor

ArmorBlock I/O

ArmorStart

871TM

Proximity

Sensor

Limit

Switch

EM

ERGENC

Y

20’

RightSight

Photoelectric

Sensor

CompactBlock I/O

Parts Catalog Table

Connectors RA Part number Description

1485P-K1GK4

Flat cable to Thin Round Cable

Converter, IDC

1485P-K1TLR4

Power Tap

1485P-K1TG4

Trunk-line Connector IDC

1485P-K1DL4

Drop-line Connector IDC

1485P-K1TR4

Terminating Resistor IDC

1485A-KCrimp

Crimping Pliers

1485P-K1G4-Y5

5-pin Open Style Connector IDC

Media

RA Part number Description
1485C-P1W100

IP20 Flat Media Cable Spool, 100 meters

1485C-P1W300

IP20 Flat Media Cable Spool, 300 meters

1485C-P1W600

IP20 Flat Media Cable Spool, 600 meters

LINK 1

LINK 2

MOD

NET

0

2

1

13

14

4

3

11

12

6

5

P
W
R

9

7

8

0

2

4

6

8

X10

X1

X100

10

15

0

2

4

6

8

0

2

4

6

8

1732 ArmorBlock I/O

• Digital 24V DC I/O

• 8 or 16 points per block with 1 block

per node for greater module density

• Mounts anywere on machine, resulting

in shorter cable runs

871TM Inductive Proximity Sensor

• 10-30V DC or 40-250V AC/DC

• NEMA 4X, IP67 all models

• 1200psi washdown

• Available sensing: Standard,

Extended/Equal, FERROUS only,

Non FERROUS only

PowerTap has Built-in

Terminating Resistor

Wire Way

KwikLink Lite Media is rated for Class 2 operation and

all applicable NEC codes should be adhered to during its

installation. The cabling system is rated IP20 and it

should be installed inside an enclosure or in a dry and

oil free environment. Use of a wire tray is recommended.

RightSight

RightSight DeviceNet Senors:

• Strobing and COS protocols

• ON delay, OFF delay and one shot timers

• Adjustable counter with output

• Adjustable motion detection

• Dual margin threshold diagnostics

• Autobaud

Stack Lights

• Control Tower™ stack lights provide

multi-status indiction of your application

• Available in three sizes: 30mm, 50mm,

and 70mm with UL Type 4/4X/13/IP65

ratings

Powered

Roller

Controller

START

STOP

1799

• The 1799D has universal inputs

• DeviceLogix allows local logic execution that enables the fast

speed required for high performance conveying

• Configuration is done through RSNetWorx for DeviceNet

KwikLink Lite

Terminator

DeviceNet KwikLink Lite Media Guidelines

KwikLink Lite

Cable Color Code

Data Rates

125k baud

250k baud

500k baud

KwikLink Lite Trunk Distance 350m

150m

55m

Number of Nodes

64

Max. Drop Length

6.1m

Cumulative Drop

159m

78m

39m

193-DNCT

DeviceNet

Configuration

Terminal

7

A

ESC

B

SEL

C

RESET

D

E

8

9

F1

F2

F3

F4

4

5

6

1

2

3

F

Copy

Exp

.

Help

0

SHIFT

Paste

+/-

24 Vdc Class 2

Assembly

Power Supply

Allen-Bradley

To plantwide network

infrastructure

193-EE

Electronic Overload

CompactLogix with

1769-SDN/B DeviceNet scanner

Publication IASIMP-QR021A-EN-P—May, 2010

IASIMP-QR021A-EN-P:Layout 1 5/26/10 3:06 PM Page 1