ControlNet Comm Glass Fiber Adapter Kit

Connecting the ControlNet Comm Glass Fiber Adapter Kit to the Network and the Reach Drive

1.

Remove power from the drive.

2.

Use static control precautions.

3.

Connect the ControlNet Fiber cable to the adapter. A 1786-RPFM is recommended for the
CNM-CNETGF-11.

4.

Connect one end of the interface cable to the adapter and the other end to the Reach Drives shown in
Figure 3.

Figure 3 - CNM-CNETGF-11 Mounted to Reach Drive

!

ATTENTION: DC bus capacitors retain hazardous voltages after input power has been
disconnected. After disconnecting input power, wait five (5) minutes for the DC bus capacitors to
discharge and then check the voltage with a voltmeter to ensure the DC bus capacitors are
discharged before touching any internal components. Failure to observe this precaution could
result in severe bodily injury or loss of life.

!

ATTENTION: Risk of equipment damage exists. The ControlNet adapter contains ESD
(Electrostatic Discharge) sensitive parts that can be damaged if you do not follow ESD control
procedures. Static control precautions are required when handling the adapter. If you are
unfamiliar with static control procedures, refer to Guarding Against Electrostatic Damage,
Publication 8000-4.5.2.

PLUG CABLE
INTO BRIDGE PCB

SEE DETAIL

INSERT ONE END OF THE INTERFACE
CABLE INTO THE COMM CARD HEADER,
AND THEN INSERT THE OTHER END INTO
THE BRIDGE PC BOARD HEADER

INSERT AND TWIST TO SECURE THE
ST STYLE FIBER OPTIC CABLES INTO
COMM CARD

REACH DRIVE

ADAPTER