Rockwell Automation T8431 Trusted TMR Analogue Input Module User Manual
Sds-8431, Trusted, Industrial control system trusted
 
SDS-8431
Trusted
TM
Industrial Control System
Trusted
TM
TMR Analogue Input Module-T8431
Issue 5 Jan 2006
FRONT PANEL
DESCRIPTION
 
The Trusted
TM
TMR Analogue Input
module interfaces to 40 single-ended 
field input devices. A wide input 
range and programmable thresholds 
allow the module to be used in most 
voltage or current configurations. 
Comprehensive diagnostic tests are 
performed on each input channel, 
including tests for out of range values 
and stuck at failures. Fault tolerance 
is achieved through Triple Modular 
Redundancy (TMR) within the same 
module for each of the 40 input 
channels. 
The module can apply a digital filter to 
each input channel. Individual 
channels can be configured for high 
noise immunity (50Hz or 60Hz 
rejection), low noise immunity (fast 
response), or pass-through operation 
(no filtering). 
Each
input
channel
has
four
configurable state thresholds, which 
may be assigned to SOE reporting. A 
change of state triggers an SOE 
entry. The on-board Sequence of 
Events (SOE) reporting has a 
resolution of 1ms. 
Each triplicated section of the 
module, referred to as a slice, 
conditions and measures each 
channel independently. Each slice is 
opto-isolated up to 2500V dc. Each 
slice sends its data to a safety layer 
hardware voter that presents the 
information from all three slices to the 
Trusted
TM
TMR Processor. When a
fault is detected on a slice of the 
module, 
the
Trusted
TM
TMR
Processor
will
flag
the
error,
indicating the need to replace the 
module. The Trusted
TM
TMR
Processor will continue to use the 
information provided by the remaining 
two slices until a replacement module 
is available. Replacement modules 
can be located in a standby slot next 
to the module or in a designated 
SmartSlot 
with
a
temporary
connection to the same Trusted
TM
Termination Assembly.
Modules may be placed in any I/O 
module slot in a Trusted
TM
Processor
Chassis or Expander chassis. Once 
the I/O module configuration is set, 
mechanical keying is available on all 
I/O modules to prevent inserting a 
module into an incorrect slot. 
Configuration of the module is carried 
out using the Trusted
TM
Toolset
running
on
an
Engineering
Workstation. Once configured and 
loaded into the Trusted
TM
Controller,
replacement modules are on-line 
educated by the TMR Processor. 
 
FEATURES 
40 TMR input channels per 
module 
Comprehensive diagnostics 
and self-test 
2500V dc Opto-Isolation
Digital signal filtering on a per 
channel basis 
Four user configurable 
thresholds per channel 
On-board 1ms resolution 
Sequence of Events reporting 
Hot replaceable
Front panel status LEDs for 
each channel 
Module fault and status 
indicators 
IEC 61508, SIL 3 safety 
applications