Module status indicator – Rockwell Automation 1440-ACNR XM ControlNet Adapter User Manual
Page 42

42
Publication ICM-UM001C-EN-E - March 2013
Chapter 4
Troubleshoot the Module
Module Status Indicator
ControlNet A and ControlNet B Status Indicators Together
ControlNet A or ControlNet B Status Indicator Individually
State
Probable Cause
Off
No power applied to device
Alternating Red/Green
LED power up test (module self-test)
Flashing Red
Recoverable fault has occurred:
•
Firmware (NVS) download is currently in progress
•
The MAC ID has changed
•
CPU load has been exceeded
Solid Red
Unrecoverable fault has occurred:
•
Self test failure (checksum failure at power up, RAM test
failure at power up
•
Firmware fatal error
Solid Green
Device is operating correctly (normal mode)
State
Probable Cause
Both Off
Reset, no power or entire network interface deactivated
Alternating Red/Green
Self test mode
Alternating Red/Off
Bad/invalid node configuration (such as duplicate MAC ID)
Both Red
Failed link interface or failed module
State
Probable Cause
Off
Channel is disabled or channel is not supported
Flashing Red/Green
Invalid link configuration
Flashing Red/Off
Severe Link error - link fault or no MAC frames received
Flashing Green/Off
Temporary channel error or listen-only
Solid Green
Normal operation - MAC frames are being received without
detected errors